DESCRIPTION
Buyer to pick up or contact us for shipping options | |
---|---|
Cycling Capacity 20 hour rate | 125 Amp Hours |
Reserve Capacity | |||
---|---|---|---|
@ 25 Amps | 200 minutes | @ 75 Amps | 45 minutes |
Mechanical Specifications | |
---|---|
Group Size | 31 |
Terminal Type | M8 (w/ TP08 Brass AP Included) |
Total Height | 8.66" (220 mm) |
Height | 8.43" (214 mm) |
Width | 6.77" (172 mm) |
Length | 12.91" (328 mm) |
Weight | 72.3 lbs (32.8 kg) |
Case Type | ABS Plastic - Flame Res Rating UL94-HB |
Discharge Table (Constant Current) | ||
---|---|---|
Time | Amps | Rate |
20 hr | 5.8 | 0.05 CA |
10 hr | 10.4 | 0.1 CA |
8 hr | 11.9 | 0.13 CA |
5 hr | 18.2 | 0.25 CA |
3 hr | 27 | 0.33 CA |
2 hr | 33 | 0.5 CA |
1 hr | 62.1 | 1 CA |
Electrical Specifications | |
---|---|
Nominal Voltage | 12 Volt |
Capacity @ 100 hour rate | 130 AH |
Capacity @ 20 hour rate | 115 AH |
Capacity @ 10 hour rate | 104 AH |
Capacity @ 5 hour rate | 91 AH |
CCA | 760 |
CA or MCA | 910 |
Short Circuit Current | 2830 Amps |
Internal Resistance | 3.8m Ω |
Charge Voltages | ||||
---|---|---|---|---|
Battery Voltages | ||||
Charge Stage | 12V | 24V | 36V | 48V |
Bulk | 14.7 V | 29.4 V | 44.1 V | 58.8 V |
Absorption | 14.7 V | 29.4 V | 44.1 V | 58.8 V |
Float | 13.6 V | 27.2 V | 40.8 V | 54.6 V |
TC Factor: -4mV/°C/cell |
Temperature Range Specifications | ||
---|---|---|
Condition | Recommended | Maximum |
Storage | -15°C to 50°C | -40°C to 71°C |
Operation | -15°C to 40°C | -40°C to 71°C |
Charge with TC | -15°C to 50°C | -40°C to 71°C |
Charge without TC | 0°C to 40°C | -15°C to 50°C |
Terminal Torque Specifications | |||
---|---|---|---|
Terminal Type | ft-lbs | in-lbs | Nm |
AP | DT (AP) | M6 | M6M (stud) | TP07 (AP) | TP08 (AP) | 4.2 - 6.0 | 50-70 | 5.6 - 7.9 |
FR45 | 6.0 - 7.5 | 70-90 | 7.9 - 10.1 |
M8 | LT | 7.1 - 8.0 | 85-95 | 9.6 - 10.7 |
DT (stud) | M10M (stud) | 9.2 - 10.4 | 110-125 | 12.2 - 14.0 |